September 2016

Conference Paper

Regional Climate Zone Modeling of a Commercial Absorption Heat Pump Hot Water Heater – Part 1: Southern and South Central Climate Zones

By:
Geoghegan, Patrick J; Shen, Bo ; Keinath, Christopher; Garrabrant, Michael
Publication Date:
September 10, 2016
Conference Name:
16th International Refrigeration and Air Conditioning Conference at Purdue
Conference Location:
West Lafayette, Indiana, United States of America

Abstract

Commercial hot water heating accounts for approximately 0.78 Quads of primary energy use with 0.44 Quads of this amount from natural gas fired heaters. An ammonia-water based commercial absorption system, if fully deployed, could achieve a high level of savings, much higher than would be possible by conversion to the high efficiency nonheat-pump gas fired alternatives. In comparison with air source electric heat pumps, the absorption system is able to maintain higher coefficients of performance in colder climates. The ammonia-water system also has the advantage of zero Ozone Depletion Potential and low Global Warming Potential. A thermodynamic model of a single effect ammonia-water absorption system for commercial space and water heating was developed, and its performance was investigated for a range of ambient and return water temperatures. This allowed for the development of a performance map which was then used in a building energy modeling software. Modeling of two commercial water heating systems was performed; one using an absorption heat pump and another using a condensing gas storage system. The energy and financial savings were investigated for a range of locations and climate zones in the southern and south central United States. A follow up paper will analyze northern and north/central regions. Results showed that the system using an absorption heat pump offers significant savings.


Related Researchers